AUTIXON / ELECTRONICS & INSTRUMENTATION

PT100 / PT1000 Calculator

Convert temperature and resistance with optional two-wire lead correction.

ParametersLIVE CALCULATION

Decimal commas and decimal points accepted.
PT100100.0 °CΩProbe
Concept diagram · not to scale
Temperature
100 °C
Sensor resistance
138.5055 Ω
Terminal resistance
138.5055 Ω
Lead correction
0 Ω

FormulaR(T) = R₀ [1 + A T + B T² + C(T − 100)T³]; C term only below 0 °C

Method & assumptions

Callendar–Van Dusen model for platinum α = 0.00385: A = 3.9083×10⁻³, B = −5.775×10⁻⁷, C = −4.183×10⁻¹². Supported mathematical range: −200…850 °C.

Two-wire mode adds or subtracts the known total lead resistance. Compensated mode assumes lead effects have already been removed. Sensor tolerance, self-heating and instrument errors are not included; the probe’s usable range may be narrower.

Analog Devices — CN0383 RTD transfer function ↗

PT100 and PT1000 resistance–temperature reference

A PT100 has a nominal resistance of 100 Ω at 0 °C; a PT1000 has 1,000 Ω at the same temperature. This converter uses the platinum α = 0.00385 Callendar–Van Dusen model rather than a constant ohms-per-degree approximation.

Using the calculator

  1. Select PT100 or PT1000 and choose temperature-to-resistance or resistance-to-temperature conversion.
  2. For a raw two-wire measurement, enter the total resistance of both leads. It is subtracted before calculating temperature.
  3. For a compensated resistance value, choose sensor only / compensated so lead resistance is not subtracted twice.
Nominal RTD values (α = 0.00385)
TemperaturePT100PT1000
−200 °C18.52008 Ω185.2008 Ω
−100 °C60.25584 Ω602.5584 Ω
0 °C100 Ω1000 Ω
100 °C138.5055 Ω1385.055 Ω
200 °C175.856 Ω1758.56 Ω
850 °C390.481125 Ω3904.81125 Ω

Frequently asked questions

What resistance should a PT100 read at 100 °C?

The nominal model gives 138.5055 Ω for a PT100 and 1385.055 Ω for a PT1000. A real reading also depends on sensor tolerance, wiring and the measuring instrument.

How does two-wire lead correction work?

If the terminal reading is 140.5055 Ω and both leads total 2 Ω, the corrected PT100 resistance is 138.5055 Ω, corresponding to 100 °C in the nominal model.

Does the −200 to 850 °C calculation range apply to every probe?

No. It is the range supported by the mathematical model. Check the actual probe’s construction, rated temperature range and tolerance. The calculation does not include self-heating or measurement uncertainty.