Three-Phase Power

Solve kW, kVA, kvar, current or power factor.

Calculation inputs

Illustrative example values — replace them before any engineering decision.

Engineering results

Active power106.002 kW

Method and traceability

Balanced system: S=√3·U·I; P=S·cosφ; Q=√(S²−P²).

Visible assumptions: copper ρ₂₀ 0.0175 and aluminium 0.0282 Ω·mm²/m; copper α 0.00393 and aluminium 0.00403/°C. Reactance, density, factors and thresholds remain editable.

Screening lists — sections: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630 mm²; breakers: 2, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600 A; transformers: 25, 50, 100, 160, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500, 3150 kVA.

Final design must verify applicable IEC 60364 requirements, actual thermal conditions, short circuit, shock protection, selectivity, starting, harmonics and local rules.

IEC 60364-5-52 ↗Guide — voltage drop ↗

Need a complete electrical study?AUTIXON can verify networks, protection, cables and execution documents.
Request an assessment
Engineering reference

Three-Phase Power Calculator

Solve active power, apparent power, reactive power, current, voltage or power factor from compatible three-phase quantities.

Calculation method

The selected output determines which compatible input pair or triplet is used. The engine does not infer missing quantities beyond the displayed balanced three-phase relationships.

Formulas used

  • P = √3 × V × I × cosφ / 1,000; S = √3 × V × I / 1,000
  • Q = √(S² − P²); cosφ = P / S

Worked example

Example: 400 V, 180 A and cosφ 0.85 give about 106 kW in a balanced three-phase system.

How to interpret the result

Check whether the displayed value is kW, kVA, kvar, A, V or a unitless power factor before using it downstream.

Common mistakes

  • Confusing line-to-line and phase voltage.
  • Treating kW and kVA as identical.

Scope and limitations

  • The formulas assume a balanced sinusoidal three-phase system.

Frequently asked questions

What is the difference between kW and kVA?

kW is active power; kVA is apparent power. Power factor relates them.

Why does √3 appear?

It relates line quantities to total power in a balanced three-phase system.

Can kvar be calculated if kW exceeds kVA?

No. That combination is physically inconsistent and the result is withheld.